Secondary Surge Protector: Spd At The Junction Of Lpz 1 And Lpz 2 (surge Protector On The Input Side Of The Switch Box/cabinet)
1) Maximum continuous operating voltage Uc: 300~385V
2) Rated operating voltage Un: 230/400 Vac
3) Nominal discharge current In: ≥40kA ( 8/20μs )
4) Maximum discharge current Imax: ≥80kA ( 8/20μs )
5) Voltage protection level Up: L-N≤1.8Kv, N-PE≤1.5Kv;
6) Protection mode: 3+1 mode
7) With remote indication contacts, installed on standard DIN rail;
8) Composite SPD, no leakage current and no continuous current;
9) Equipped with the same brand backup protection device as the surge protector, with the Imax impact current of the SPD without disconnection capability, the SSD must have a working status indication window.